Planned Power Outage

ATEK Team
Planned Power Outage

Disabling all site alarms is no small feat.

At ATEK, there are two types of alarms: one alarm type for sensors and one alarm type for transmitters/gateway.

You will therefore have at minimum 5 alarms during the intervention:

  • A threshold exceedance
  • An inactive sensor
  • A power loss - transmitter
  • An inactive gateway
  • An inactivity - transmitter

Sensor Operation

To avoid triggering the threshold alarm, you must inhibit the sensor.

To avoid triggering the inactivity alarm, you must put into maintenance. However, this action stops data recording.

If you want to preserve the data and avoid triggering the inactivity alarm, you must remove the sensor from alarm condition.

Transmitter Operation

To avoid triggering the power failure alarm and the inactivity alarm, you must remove transmitters from alarm condition.

Transmitter alarms cannot be inhibited or put into maintenance.

Gateway Operation

To avoid triggering the inactivity alarm, you must remove gateways from alarm condition.

Gateway alarms cannot be inhibited or put into maintenance.

Important

Keep track of your interventions to make the opposite configurations after the manipulations.

💡 Le saviez-vous?

Tranquillité d'esprit pour vos actifs critiques

La surveillance automatisée d'ATEK a sauvé des centaines de milliers de doses de vaccins pendant la COVID-19 grâce à un historique complet des températures - transformant 'tout jeter' en 'évaluer et décider'.

Partager cet article :
Retour aux articles
AT

ATEK Team

Équipe ATEK

Expert en surveillance environnementale, conformité réglementaire et gestion de la chaîne du froid pour les industries pharmaceutiques et de santé.

Besoin de solutions de surveillance environnementale?

Contactez ATEK pour une démo personnalisée et découvrez comment nous pouvons aider à protéger vos environnements critiques.

Demander une démo